Room Occupancy Schedule Changes

Please submit a Room Occupancy Schedule Change Request to have the set-back / set-up temperature schedule for your area adjusted outside of regular office hours.

As an energy conservation measure SFU sets-back / sets-up the temperature when the buildings are unoccupied. i.e.: no heating above17C, no cooling below 28C. During the occupied period, each space for human comfort is maintain at 21C during the heating season and 26C during the cooling season.

For example, you may request to adjust the setback temperature schedule if:

  • You are planning to work over the weekend at your work space
  • Space temperature needs to be maintain over the winter break
  • Exams will be held over the weekend
  • You are holding an event that will go beyond regular office hours or over the weekend (no need to create a second request if already requested on your Event Setup Request)
  • Research facilities and labs need to be controlled to satisfy research requirements